Endress+Hauser 21
The following is recommended as a socket:
Binder, series 763, part no. 79 3440 35 05
Alternatively: Phoenix part no. 1669767 SAC-5P-M12MS
With the order code for "Output", option B: 4-20 mA HART, pulse/frequency/switch output
With the order code for "Output", option N: EtherNet/IP
When using the device in a hazardous location: Use a suitably certified socket.
4-20 mA HART with pulse/frequency/switch output
4-20 mA HART with pulse/frequency/switch output (on the device side)
A0016810
Pin Assignment Coding Plug/socket
1 + 4-20 mA HART (active) A Socket
2 - 4-20 mA HART (active)
3 + Pulse/frequency/switch output
(passive)
4 - Pulse/frequency/switch output
(passive)
5 Grounding/shielding
Recommended plug: Binder, series 763, part no. 79 3439 12 05
When using the device in a hazardous location: Use a suitably certified plug.
PROFIBUS DP
PROFIBUS DP, non-hazardous area and Zone 2/Div. 2 (on the device side)
3
2
4
1
5
A0016811
Pin Assignment Coding Plug/socket
1 B Socket
2 A PROFIBUS DP
3
4 B PROFIBUS DP
5 Grounding/shielding
Recommended plug: Binder, series 763, part no. 79 4449 20 05
When using the device in a hazardous location: Use a suitably certified plug.
Modbus RS485
Modbus RS485, non-hazardous area and Zone 2/Div. 2 (on the device side)
3
2
4
1
5
A0016811
Pin Assignment Coding Plug/socket
1 B Socket
2 A Modbus RS485
3
4 B Modbus RS485
5 Grounding/shielding
Recommended plug: Binder, series 763, part no. 79 4449 20 05
When using the device in a hazardous location: Use a suitably certified plug.