Proline Promag P 100
20 Endress+Hauser
EtherNet/IP connection version
Order code for "Output", option N
Depending on the housing version, the transmitters can be ordered with terminals or device plugs.
Order code for
"Housing"
Connection methods available
Possible options for order code
"Electrical connection"
Output
Power
supply
Option A Device plug
(→  22)
Terminals Option L: plug M12x1 + thread NPT ½"
Option N: plug M12x1 + coupling M20
Option P: plug M12x1 + thread G ½"
Option U: plug M12x1 + thread M20
Option A Device plug
(→  22)
Device plug
(→  22)
Option Q: 2 x plug M12x1
Order code for "Housing":
Option A: compact, coated aluminum
L
L
1
2
+
_
1
2
A0017054
 5 EtherNet/IP terminal assignment
1 Power supply: DC 24 V
2 EtherNet/IP
Order code for
"Output"
Terminal number
Power supply Output
2 (L-) 1 (L+) Device plug M12x1
Option N DC 24 V EtherNet/IP
Order code for "Output":
Option N: EtherNet/IP
Pin assignment, device plug
Order codes for the M12x1 plug, see the "Order code for electrical connection" column:
4-20 mA HART, pulse/frequency/switch output (→  17)
Modbus RS485 (→  19)
EtherNet/IP (→  20)
Supply voltage
Supply voltage for all communication types (on the device side)
A0016809
Pin Assignment Coding Plug/socket
1 L+ DC24 V A Plug
2
3
4 L- DC24 V
5 Grounding/shielding