Proline Promag P 100
Endress+Hauser 27
3
4...20 mA
4
521
+
-
6
4...20 mA
+
-
7
3
4
52
+
-
-
+
A0019830
13 Connection example for HART input (master mode) via current output (active)
1 Automation system with current input (e.g. PLC).
Prerequisite: automation system with HART version 6, HART commands 113 and 114 can be processed.
2 Cable shield, observe cable specifications (→ 29)
3 Resistor for HART communication (≥ 250 Ω): observe maximum load (→ 8)
4 Connection for HART operating devices (→ 48)
5 Analog display unit
6 Transmitter
7 Sensor for external measured variable
Potential equalization Requirements
Please consider the following to ensure correct measurement:
• Same electrical potential for the fluid and sensor
• Company-internal grounding concepts
• Pipe material and grounding
For devices in hazardous locations, please observe the guidelines in the Ex documentation (XA).
Connection examples for standard situations
Metal, grounded pipe
A0016315
14 Potential equalization via measuring tube
Connection example in special situations
Unlined and ungrounded metal pipe
This connection method also applies in situations where:
• The customary potential equalization is not used
• Equalizing currents are present