Electrical connection Connecting the transmitter
1 2
A
A0019824
A Housing version: compact, aluminum coated
1 Cable entry or device plug for signal transmission
2 Cable entry or device plug for supply voltage
Terminal assignment (→  17)
Pin assignment, device plug (→  20)
In the case of device versions with a connector, the transmitter housing does not need to be
opened to connect the signal cable or power supply cable.
Connection examples
Current output 4-20 mA HART
4
4...20 mA
+
5
2
1
3
6
+
_
A0016800
 6 Connection example for 4-20 mA HART current output (active)
1 Automation system with current input (e.g. PLC)
2 Cable shield, observe cable specifications (→  29)
3 Connection for HART operating devices (→  48)
4 Resistor for HART communication (≥ 250 Ω): observe maximum load (→  8)
5 Analog display unit: observe maximum load (→  8)
6 Transmitter