Proline Promag P 100
Endress+Hauser 7
Nominal
diameter
Recommended
flow
Factory settings
min./max. full scale value
(v ~ 0.3/10 m/s)
Current output full scale
value
1)
(v ~ 2.5 m/s)
Pulse value
1)
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
[mm] [in] [dm
3
/min] [dm
3
/min] [dm
3
] [dm
3
/min]
500 20 220 to 6 600 m
3
/h 2 000 m
3
/h 0.25 m
3
30 m
3
/h
600 24 310 to 9 600 m
3
/h 2 500 m
3
/h 0.3 m
3
40 m
3
/h
1) HART only
Flow characteristic values in US units
Nominal
diameter
Recommended
flow
Factory settings
min./max. full scale value
(v ~ 0.3/10 m/s)
Current output full scale
value
1)
(v ~ 2.5 m/s)
Pulse value
1)
(~ 2 pulse/s)
Low flow cut off
(v ~ 0.04 m/s)
[in] [mm] [gal/min] [gal/min] [gal] [gal/min]
½ 15 1.0 to 27 6 0.1 0.15
1 25 2.5 to 80 18 0.2 0.25
1 ½ 40 7 to 190 50 0.5 0.75
2 50 10 to 300 75 0.5 1.25
3 80 24 to 800 200 2 2.5
4 100 40 to 1 250 300 2 4
6 150 90 to 2 650 600 5 12
8 200 155 to 4 850 1200 10 15
10 250 250 to 7 500 1500 15 30
12 300 350 to 10 600 2400 25 45
14 350 500 to 15 000 3600 30 60
16 400 600 to 19 000 4800 50 60
18 450 800 to 24 000 6000 50 90
20 500 1 000 to 30 000 7500 75 120
24 600 1 400 to 44 000 10500 100 180
1) HART only
To calculate the measuring range, use the Applicator sizing tool (→ 55)
Recommended measuring range
"Flow limit" section (→ 40)
Operable flow range
Over 1000 : 1
Input signal Fieldbuses
To increase the accuracy of certain measured variables or to calculate the corrected volume flow, the
automation system can continuously write different measured values to the measuring device via
Modbus RS485, EtherNet/IP or HART input:
• Process pressure or fluid temperature to increase accuracy (e.g. external values from Cerabar M,
Cerabar S or iTEMP)
• Reference density for calculating the corrected volume flow