Proline Promag P 100
Endress+Hauser 9
Number of switching
cycles
Unlimited
Assignable functions Off
On
Diagnostic behavior
Limit value:
Off
Volume flow
Mass flow
Corrected volume flow
Flow velocity
Conductivity
Corrected conductivity
Totalizer 1-3
Temperature
Electronics temperature
Flow direction monitoring
Status
Empty pipe detection
Low flow cut off
PROFIBUS DP
Signal encoding NRZ code
Data transfer 9.6 kBaud…12 MBaud
Modbus RS485
Physical interface In accordance with EIA/TIA-485-A standard
Terminating resistor Integrated, can be activated via DIP switch on the transmitter electronics module
EtherNet/IP
Standards In accordance with IEEE 802.3
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output
4-20 mA
Failure mode Selectable (as per NAMUR recommendation NE 43):
Minimum value: 3.6 mA
Maximum value: 22 mA
Defined value: 3.59 to 22.5 mA
Actual value
Last valid value
HART
Device diagnostics Device condition can be read out via HART Command 48
Pulse/frequency/switch output
Pulse output
Failure mode Choose from:
Actual value
No pulses