Proline Promag P 100
22 Endress+Hauser
EtherNet/IP
EtherNet/IP (on the device side)
3
2
4
1
A0016812
Pin Assignment Coding Plug/socket
1 + Tx D Socket
2 + Rx
3 - Tx
4 - Rx
Recommended plug:
Binder, series 763, part no. 99 3729 810 04
Phoenix, part no. 1543223 SACC-M12MSD-4Q
When using the device in a hazardous location: Use a suitably certified plug.
Supply voltage Transmitter
For device version with all communication types: DC 20 to 30 V
The power unit must be tested to ensure it meets safety requirements (e.g. PELV, SELV).
Power consumption
Transmitter
Order code for
"Output"
Maximum
Power consumption
Option B: 4-20mA HART, pulse/frequency/switch output 3.5 W
Option L: PROFIBUS DP 3.5 W
Option M: Modbus RS485 3.5 W
Option N: EtherNet/IP 3.5 W
Current consumption Transmitter
Order code for
"Output"
Maximum
Current consumption
Maximum
switch-on current
Option B: 4-20mA HART, pul./
freq./switch output
145 mA 18 A (<0.125 ms)
Option L: PROFIBUS DP 145 mA 18 A (<0.125 ms)
Option M: Modbus RS485 90 mA 10 A (<0.8 ms)
Option N: EtherNet/IP 145 mA 18 A (<0.125 ms)
Power supply failure
Totalizers stop at the last value measured.
Depending on the device version, the configuration is retained in the device memory or in the
plug-in memory (HistoROM DAT).
Error messages (incl. total operated hours) are stored.