Endress+Hauser Proline Promag P 100 - Connecting the Transmitter and Potential Equalization

Endress+Hauser Proline Promag P 100
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Proline Promag P 100
Endress+Hauser 25
PROFIBUS DP
2
1
A
B
A
B
A
B
3
3
A0021429
 9 Connection example for PROFIBUS DP, non-hazardous area and Zone 2/Div. 2
1 Control system (e.g. PLC)
2 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications (→  30)
3 Distribution box
4 Transmitter
If baud rates > 1.5 MBaud an EMC cable entry must be used and the cable shield must continue
as far as the terminal wherever possible.
Modbus RS485
2
1
A
B
A
B
A
B
3
4
4
A0016803
 10 Connection example for Modbus RS485, non-hazardous area and Zone 2/Div. 2
1 Control system (e.g. PLC)
2 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications (→  30)
3 Distribution box
4 Transmitter