Commissioning Proline Promass E 100 Modbus RS485
60 Endress+Hauser
Parameter Prerequisite Description
Selection/
User entry
Factory setting
Volume unit The following option
is selected in the
Assign process
variable parameter:
Volume flow
Select the unit for
volume.
Result
The selected unit is
taken from:
Volume flow unit
Unit choose list Country-dependent
• l
• gal (us)
Corrected volume
unit
The following option
is selected in the
Assign process
variable parameter:
Corrected volume
flow
Select the unit for
standard volume.
Result
The selected unit is
taken from:
Corrected volume
flow unit
Unit choose list Country-dependent:
• Nl
• Scf
Totalizer operation
mode
One of the following
options is selected in
the Assign process
variable parameter:
• Mass flow
• Volume flow
• Corrected volume
flow
Select totalizer
calculation mode.
• Net flow total
• Forward flow
total
• Reverse flow total
Net flow total
Failure mode One of the following
options is selected in
the Assign process
variable parameter:
• Mass flow
• Volume flow
• Corrected volume
flow
Specify the behavior
of the totalizer in
the event of a device
alarm.
• Stop
• Actual value
• Last valid value
Stop
10.5 Simulation
The Simulation submenu enables you to simulate, without a real flow situation, various
process variables in the process and the device alarm mode and to verify downstream
signal chains (switching valves or closed-control loops).
Navigation path
"Diagnostics" menu → Simulation
Simulation
→
Assign simulation process variable
Value process variable
Simulation device alarm