Commissioning Proline Promass F 500 Modbus RS485
136 Endress+Hauser
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry / User
interface
Factory setting
Assign simulation process variable Select a process variable for
the simulation process that is
activated.
Off
Mass flow
Volume flow
Corrected volume
flow
Density
Reference density
Temperature
Concentration
*
Target mass flow
*
Carrier mass flow
*
Off
Process variable value One of the following options is
selected in the Assign
simulation process variable
parameter (→  136):
Mass flow
Volume flow
Corrected volume flow
Density
Reference density
Temperature
Concentration
*
Target mass flow
*
Carrier mass flow
*
Enter the simulation value for
the selected process variable.
Depends on the
process variable
selected
0
Status input simulation Switch simulation of the status
input on and off.
Off
On
Off
Input signal level In the Status input simulation
parameter, the On option is
selected.
Select the signal level for the
simulation of the status input.
High
Low
High
Current input 1 to n simulation Switch simulation of the
current input on and off.
Off
On
Off
Value current input 1 to n In the Current input 1 to n
simulation parameter, the On
option is selected.
Enter the current value for
simulation.
0 to 22.5 mA 0 mA
Current output 1 to n simulation Switch the simulation of the
current output on and off.
Off
On
Off
Value current output 1 to n In the Current output 1 to n
simulation parameter, the On
option is selected.
Enter the current value for
simulation.
3.59 to 22.5 mA 3.59 mA
Frequency output simulation 1 to n In the Operating mode
parameter, the Frequency
option is selected.
Switch the simulation of the
frequency output on and off.
Off
On
Off
Frequency value 1 to n In the Frequency output
simulation 1 to n parameter,
the On option is selected.
Enter the frequency value for
the simulation.
0.0 to 12 500.0 Hz 0.0 Hz
Pulse output simulation 1 to n In the Operating mode
parameter, the Pulse option is
selected.
Set and switch off the pulse
output simulation.
For Fixed value option:
Pulse width parameter
(→  106) defines the
pulse width of the pulses
output.
Off
Fixed value
Down-counting
value
Off
Pulse value 1 to n In the Pulse output
simulation 1 to n parameter,
the Down-counting value
option is selected.
Enter the number of pulses for
simulation.
0 to 65 535 0