Proline Promass F 500 Modbus RS485 Commissioning
Endress+Hauser 97
Navigation
"Setup" menu → Communication
Communication
Bus address
→  97
Baudrate
→  97
Data transfer mode
→  97
Parity
→  97
Byte order
→  97
Failure mode
→  97
Parameter overview with brief description
Parameter Description User entry / Selection Factory setting
Bus address Enter device address. 1 to 247 247
Baudrate Define data transfer speed. 1200 BAUD
2400 BAUD
4800 BAUD
9600 BAUD
19200 BAUD
38400 BAUD
57600 BAUD
115200 BAUD
19200 BAUD
Data transfer mode Select data transfer mode. ASCII
RTU
RTU
Parity Select parity bits. Picklist ASCII option:
0 = Even option
1 = Odd option
Picklist RTU option:
0 = Even option
1 = Odd option
2 = None / 1 stop bit option
3 = None / 2 stop bits
option
Even
Byte order Select byte transmission sequence. 0-1-2-3
3-2-1-0
1-0-3-2
2-3-0-1
1-0-3-2
Failure mode Select measured value output behavior when
a diagnostic message occurs via Modbus
communication.
NaN
1)
NaN value
Last valid value
NaN value
1) Not a Number