Promag 53 PROFIBUS-DP/-PA 10 Technical data
Endress+Hauser 131
10 Technical data
10.1 Technical data at a glance
Application
Application Measuring the flow rate of fluids in closed piping systems.
A minimum conductivity of
≥ 5 µS/cm is required for measuring; the minimum
conductivity required in the case of demineralised water is
≥ 20 µS/cm.
Applications in measuring, control and regulation technology for monitoring
processes, filling and batching operations.
Function and system design
Measuring principle Electromagnetic flow measurement on the basis of Faraday’s Law.
Measuring system The measuring system consists of a transmitter and a sensor.
Two versions are available:
– Compact version
– Remote version
Transmitter
• Promag 53 (Type PROFIBUS-DP/-PA)
Sensor
• Promag W (for water / waste water applications)
DN 25...2000, hard rubber or polyurethane lining
• Promag P (for chemical and process applications)
DN 15...600, PFA or PTFE lining
• Promag H (for hygenic applications)
DN 2...100, PFA lining
Input
Measured variable Flow rate (proportional to induced voltage)
Measuring range Typically v = 0.01...10 m/s with the specified measuring accuracy
Operable flow range Over 1000 : 1
Output
Output signal PROFIBUS-DP/-PA interface:
PROFIBUS-DP/-PA in acc. with EN 50170 Volume 2, IEC 61158-2,
Profile Version 3.0
galvanically insulated
Signal on alarm PROFIBUS-DP/-PA interface:
Status and alarm messages in acc. with PROFIBUS-PA Profile Version 3.0
Current consumption 11 mA
Permissible
fieldbus voltage
9...32 V, not intrinsically safe
FDE (Fault Disconnec-
tion Electronic)
0 mA
Data transfer rate PROFIBUS-PA: supported baud rate = 31.25 kBaud
PROFIBUS-DP: supported baud rate = 9.6 kBaud...12 MBaud
Signal coding PROFIBUS-PA: Manchester II
PROFIBUS-DP: NRZ Code