EasyManua.ls Logo

Endress+Hauser Promag 53 - Configuration Examples with Simatic S7 HW-Konfig

Endress+Hauser Promag 53
177 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Promag 53 PROFIBUS-DP/-PA 6 Commissioning
Endress+Hauser 99
6.4.2 Configuration examples with Simatic S7 HW-Konfig
Example 1:
Full configuration using the manufacturer-specific GSD file
This form of configuration activates all data blocks which are supported by Promag 53.
The significance of SET_TOT and MODE_TOT is described on Page 97.
Configuration data
Byte
length
(Input)
Byte
length
(Output)
Data blocks Status Access type GSD
block
designation
GSD
Extended
block
identification
GSD
Standard
block
identification
0...4 Volume flow
+ Status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
5...9 0 + 1 Totalizer 1 +
Status +
Control
variable
active read
+
write
SETTOT_
MODETOT_
TOTAL
0xC1, 0x81,
0x84, 0x85
0xC1, 0x81,
0x84, 0x85
10...14 2 + 3 Totalizer 2 +
Status +
Control
variable
active read
+
write
SETTOT_
MODETOT_
TOTAL
0xC1, 0x81,
0x84, 0x85
0xC1, 0x81,
0x84, 0x85
15...19 4 + 5 Totalizer 3 +
Status +
Control
variable
active read
+
write
SETTOT_
MODETOT_
TOTAL
0xC1, 0x81,
0x84, 0x85
0xC1, 0x81,
0x84, 0x85
20...24 Mass flow +
Status
active read AI 0x42, 0x84,
0x08, 0x05
0x94
6...10 Display
value +
Status
active write DISPLAY_
VALUE
0x82, 0x84,
0x08, 0x05
0xA4
11 Control
variable
active write CONTROL_
BLOCK
0x20 0x20
Slot 0 AI volume flow
Slot 1
Totalizer 1 + Control variable (SET_TOT, MODE_TOT)
Slot 2
Totalizer 2 + Control variable (SET_TOT, MODE_TOT)
Slot 3
Totalizer 3 + Control variable (SET_TOT, MODE_TOT)
Slot 4
AI mass flow
Slot 5: Display value (DISPLAY_VALUE)
Slot 6: Control block (CONTROL_BLOCK) manufacturer-specific
F06-53PBxxxx-20-xx-xx-xx-000

Table of Contents

Related product manuals