Promag 53 PROFIBUS-DP/-PA 9 Trouble-shooting
Endress+Hauser 115
9.2 System and process error messages
General notes
System and process errors are permanently assigned to two different error message
types and are thus given different priorities:
Error message type Fault message:
This signal will cause the measurement operation to be immediately interrupted or
stopped!
Presentation on the PROFIBUS Fault signals will be reported to the next function
block or the control system by setting the status of the corresponding process value
to BAD.
Local display A blinking lightning bolt (
) will appear.
Error message type Notice message:
The measurement operation will continue as usual in spite of this message!
Presentation on the PROFIBUS Notice messages will be reported to the next func-
tion block or the control system by setting the status of the corresponding process
value to UNCERTAIN.
Local display A blinking exclamation point (!) will appear.
Serious system errors, e.g. a fault in the electronic module, are always evaluated by the
instrument as a fault signal and will be displayed! Simulations and the suppression of
the measured value are only reported with a Notice message.
Error messages in the configuration program (Class 2 Master)
see Table
In the Promag 53 system/process errors are recognised and reported in the Transducer
Block and Analog Input Block. The following table contains a listing of the device status
messages for the Analog Input blocks (PROFIBUS-Profile 3.0) and a description of the
device status messages which may appear on the display (Measured value Q = Meas-
urement Quality).
Error messages on the local display
see Table
.
Device status
message
Diagnosis message
(Control system)
Device status
message
(Display)
No. Initial status
Analog Input Block/
Totalizer Block
Measured
value Q /
Substatus/
alarm limit
Cause/remedy
ROM / RAM failure S CRITICAL FAILURE
# 001
1 device failure BAD
0x0F
constant
Cause:
System error. ROM / RAM error.
Error when accessing the program
memory (ROM) or random access
memory (RAM) of the processor.
Remedy:
Replace the amplifier board.
Spare parts
Page 122
Amplifier EEPROM
failure
SAMP HW EEPROM
# 011
11 device failure BAD
0x0F
constant
Cause:
System error. Measuring amplifier
has faulty EEPROM
Remedy:
Replace the amplifier board.
Spare parts
Page 122