Process transmitter system messages
On On Display shows:
E 102
The operating
parameters are
invalid or the
software version
does not correspond
with the saved
operating
parameters.
Possible cause is a
power down during
save sequence or a
software update.
E 102 All operating
parameters are reset
to factory default when
acknowledging using
the E push button.
Customer specific
settings made at the
factory are not
considered.
On On Display shows:
E 103
The calibration
value of the
analogue input or
the rear panel
temperature
measurement are
faulty. Possible
cause is a power
down during
calibration, a not
calibrated unit or
hardware defect.
E 103 Please exchange the
unit.
On On Display shows:
E 104
The calibration
value of the
analogue output is
faulty. Possible
cause is a power
down during
calibration, a not
calibrated unit or
hardware defect.
E 104 Please exchange the
unit.
On On Display shows:
E 105
The analogue input
is defective.
E 105 Please exchange the
unit.
On On Display shows:
E 106
Due to a setting up
fault an incorrect
scale setting was
made (lower and
upper values are
identical).
E 106 Please correct the set
up values.
On Flashes The 7 segment
display shows a
TEXT
The unit is in
analogue output or
alarm relay
simulation mode.
E 200 End simulation mode.
Process transmitter
74