A952 49 532310 - Rev.A
5. OPERATING MODE
The operating mode of the automation can be as-
signed using the functions selector at the side of the
unit, via other specific external devices, via specially
configured inputs and from TIMER.
■ AUTOMATIC MODE
The door opens and CLOSES AUTOMATICALLY after the
programmed pause time.
TWO-DIRECTIONAL Two-directional transit is allowed
(Internal Opening and External Opening enabled).
EXIT ONLY Only exiting is allowed (External Open
disabled).
ONLY IN Only entry is allowed (Internal Open disa-
bled).
In automatic mode, the PUSH AND GO function can
be activated as follows:
- STANDARD : pushing the door manually starts
motorised opening
- POWER ASSIST : manual opening, motorised
closing
■ MANUAL MODE
The door is free to move and can only be operated
manually. No command is active.
■ OPEN MODE
The door opens and remains open.
■ NIGHT MODE
The door closes and remains closed. External Opening
is disabled. Internal Open is enabled only in the time
interval programmed as NIGHT MODE DELAY. Open-
ing is only possible via the Key and Emergency Open
inputs.
■ INTERLOCK MODE
The opening of one door is subject to the closing of
another (§ specific Section).
6. CONFIGURABLE INPUTS
All the available inputs (IN1…IN8) can be modified
in programming according to their function and type
of contact.
A brief description of each function is given below.
■ AUTOMATIC OPENING INPUTS
When one of the following inputs is activated, the
automation opens and closes again after the pause
time. The automation does not close as long as the
input is active.
EXTERNAL OPEN Input specifically for external control
devices. The input is disabled in NIGHT or EXIT ONLY
mode.
INTERNAL OPEN Input specifically for internal control
devices. The input is disabled in ONLY IN mode. In
NIGHT mode, it is enabled only in the time interval
programmed as NIGHT MODE DELAY.
AUTOMATIC OPEN The input is disabled in NIGHT mode
(it is enabled in EXIT ONLY and ONLY IN mode).
KEY Command also enabled in NIGHT mode.
PARTIAL OPEN Opens only one leaf in the 2-leaf appli-
cation. It is NOT enabled in the NIGHT mode.
NURSE AND BED In the 2-leaf application:
- a pulse <2 s opens a single leaf.
- a pulse >2 s opens both leaves.
OPEN DELAY With the door closed, this command
opens the door after the time set in the TIME DELAY
TIME parameter (from 0 s to 60 s, default 5 s).
■ SEMI-AUTOMATIC OPENING INPUT
SEMI-AUTOMATIC OPEN
If the input is activated when the automation is closed,
the door opens and remains open. If the input is
activated when the automation is open, it closes it.
The input is NOT active in NIGHT mode.
■ EMERGENCY INPUTS
The EMERGENCY inputs have priority over any other
input, in any NON MANUAL operating condition and
mode.
- Programmed input WITHOUT MEMORY: when
the status of the input is restored, the automation
starts to operate normally again
- Programmed input WITH MEMORY: when the sta-
tus of the input is restored, a RESET has to be carried
out in order for the automation to start operating
normally again.
EMERGENCY OPEN When the input is activated, the
automation opens and remains open as long as the
emergency is active.