 14 Errors and Warnings
Code Meaning Required action Error Warn-
ing
1
Board failure Perform RESET. If the problem persists, replace the boards. x
4
Accessories power supply fault Check the accessories connection for short circuits. Check the
current drawn by the connected accessories and that maximum
indicated load is not exceeded. Perform RESET. If the problem
persists, replace the E952CL board.
x
5
FW fault Make sure that there are NO sources of electromagnetic inter-
ference that are too close to the board. Update the E952CL
board FW.
x
7
Motor fail Motor disconnected or short-circuited. Check the wiring. If the
problem persists, replace the motor.
x
9
Power supply fault / No mains power Check the voltage supplied by the power supply unit. Make sure
that there is mains power.
x
11
Closing safety FAILSAFE test failed
Check the connection and operation of the connected safety de-
vice. Check the programming of input.
x
12
Opening safety FAILSAFE test failed Check the connection and operation of the connected safety
device. Check the programming of input.
x
15
SETUP inhibited
Make sure that the Night or Manual operating mode has not been selected,
that an emergency input is not active and that the automation is NOT
operating with the battery due to a mains power failure.
x
16
Encoder fault Make sure that the encoder is connected properly. If the problem
persists, replace the motor.
x
19
Friction too high Make sure that the leaf slides smoothly. Remove any friction. x
22
Programming data corrupted Programming data NOT valid or corrupted. Repeat the program-
ming and the BUS 2easy registration.
x
24
Consecutive obstacles in closing The programmed number of consecutive obstacles in closing has
been reached. Remove the obstacle. If the problem persists,
repeat the SETUP.
x
25
Lock fault Check the connection. Remove the cause of the short circuit. x
27
Motor rotation fault
Check the motor connection.
x
31
Consecutive obstacles in opening The programmed number of consecutive obstacles in opening has
been reached. Remove the obstacle. If the problem persists,
repeat the SETUP.
x
35
BUS 2easy device fault / conflict Check the addresses of the devices. x
36
BUS 2easy short circuit / overload Check the connections of the BUS 2easy devices that are connected
and registered.
x
37
Clock battery discharged or missing Install or replace clock battery. x
39
SETUP incorrect / missing Perform SETUP. x
40
PEOPLE IN - Max. capacity reached
The maximum number of people allowed in the premises has been
reached, programmed via Simply Connect for the SAFE FLOW function.
x
41
Date / time missing TIMER date/time missing. Replace the buffer battery CR1216,
then reset the time and date.
x
44
Emergency input active Check the emergency input. x
45
TIMER enabled The TIMER is enabled on the board. x
46
TIMER function in progress A TIMER mode function is in progress. x
51
Obstacle detected when closing The notification disappears on the next movement. x
52
Obstacle detected when opening The notification disappears on the next movement. x