EasyManua.ls Logo

Fagor MCS Series - M group. Motor

Fagor MCS Series
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital Brushless AC servo drive system - Ref.0707 MCS- 65/92
Function: Shows the load percentage on the ballast resistor in a drive.
Useful for the i
2
t protection of the resistor. A value greater
than 100 % in this variable causes error E.314.
Valid values: 0 (by default), ..., 100 %.
Function: Selector that determines whether the ballast resistor is
external or internal.
Valid values:
0. External
1. Internal (by default)
M group. Motor
Function: Motor identification. The limits of certain parameters depend
on the value of MP1 (for example: The upper limit of SP10
is 110 % of the motor rated speed) like its default parameter
initialization through GC10. See command GC10. To govern
a non-Fagor motor, insert the NULL value in the first field of
MP1.
Function: Contains the torque constant of the synchronous motor,
(motor torque according to the rms current)
Valid values: 0.0,..., 10.0 Nm/Arms.
Default value: It depends on the motor connected (Nm/Arms).
KV40 USER, RO IntBallastOverload
KV41 USER, RW BallastSelect
MP1 BASIC, RW MotorType
MP2 FAGOR, RW MotorTorqueConstant
MOTOR TYPE
SIZE
SHAFT HEIGHT
MAXIMUM SPEED
WINDING
FEEDBACK TYPE
FAN
BRAKE
FLANGE
AND SHAFT

Related product manuals