MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
27
The types of devices that can be installed in the system are listed in Appendix C on
page 46.
The parameters that may be set for AutoOutput Activation are shown in the following
table.
Parameter Description Applies to
DvOut
(Device Output Type)
Type of event that will cause activation of the
output. Also, whether or not it is silenceable.
8710, 8712, 8713, 8704,
8726, 8706
AutoOutput If enabled, the detector can activate its own output
device. Otherwise, the device will only activate
when its Output Zone is activated.
8710, 8712, 8713
Device Zone The Output Zone to which the output device is
assigned.
8710, 8712, 8713, 8704,
8726, 8706
On Delay Delay in seconds between when the zone activates
and when the output device activates.
8710, 8712, 8713, 8704,
8726, 8706
Off Delay Delay in seconds between when the zone activates
and when the output device de-activates. When
used with the On Delay, this parameter can be used
to turn an output device on only for a certain period
of time when its zone is activated. If this parameter
is set to zero, the device will not deactivate
(0=infinite).
8710, 8712, 8713, 8704,
8726, 8706