119
2.4.3.3 Support Data block type
Data block type
Size
Bool
Bit
Byte
8-bit
SInt
8-bit
USInt
8-bit
Word
16-bit
Int
16-bit
UInt
16-bit
DWord
32-bit
DInt
32-bit
UDInt
32-bit
Real
32-bit
String
Length = 254 byte
Please make sure that proper setting is in TIA:
(1) [DB Properties][Attributes][ Optimized block access] is unchecked
(2) [PLC program Properties][Protection][Permit access with PUT/GET
communication from remote partner (PLC,HMI,OPC,] is checked.
2.4.3.4 Connecting to HMI
Configuring IP Address on PLC
Use the application TIA V13 Step Basic to configure the IP address on the PLC.
Open a new project and add the device to be configured.
In the Project tree sidebar, select the device and navigate to the Online menu option.
Under the Online menu option, select Extend Download to Device. Select the
appropriate network interfaces and check Show all accessible devices. The application
will scan the network for the device. When the device shows up, select it.