EasyManua.ls Logo

FATEK P5070S - Page 30

FATEK P5070S
224 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
Signal Level
RS485
Baud Rate
19200
Data Length
7
Stop Bit
1
Parity
Even
PLC Station No.
1
TX Control
Form1
Without CR,LF
Checksum
Yes
Communication Method
Computer Link
2.2.2.2 Memory Resource Review
Device
Description
Data bit
Min.
Max.
X
Input Discrete
1
0
377
Y
Output Relay
1
0
377
M
Internal Relay
1
0
3071
SM
Special Relay
1
8000
8255
S
Step Relay
1
0
999
TS
Timer Discrete
1
0
255
CS
Counter Discrete
1
0
199
WX
Input Discrete
16
0
360
WY
Output Relay
16
0
360
WM
Internal Relay
16
0
3056
WS
Step Relay
16
0
976
TN
Timer Memory
16
0
255
CN
Counter Memory
16
0
199
D
Data Register
16
0
7999
SD
Special Data Register
16
8000
8255
DCN
Counter Memory
32
200
255
2.2.2.3 Connecting to HMI
Configuring the PLC
Use MELSOFT GX Works2 to configure the port of the PLC.
Under the Online menu option, select Read from PLC
Select the FXCPU PLC series.

Related product manuals