2. Commissioning
2−44
Festo P.BE−CPX−FB13−EN en 0811c
When the field bus system is switched on, the CPX terminal is
parameterised as Start parameterisation" by parameter set
1 saved in the PROFIBUS master. The field bus node then
distributes the parameters by module to the CPX modules 2.
Note
The number of start parameters is limited, depending on
the software version of the CPX−FB13.
Pay attention to the behaviour of the CPX−FB13:
Up to and including software version 15:
A maximum of 172 start parameters are possible. If the
maximum number is exceeded, no fault message will be
issued. The CPX
terminal does not start and the BF LED
flashes. Therefore, check the Start parameterisation
before commissioning.
Starting with software version 22:
A maximum of 224 start parameters are possible. If the
maximum number is exceeded, the configuration cannot
be loaded into the field bus node. A fault message is
output (see Fig.2/18).
A
list of the possible Start parameters can be found in
appendix A.2.