2. Commissioning
2−37
Festo P.BE−CPX−FB13−EN en 0811c
2.1.5 Configuration in the Remote Controller operating mode
If there is an FEC in your CPX terminal, you can operate the
field bus node in the Remote Controller" operating mode.
The field bus node occupies 8 bytes of inputs and 8 bytes of
outputs. These are available for the control program in the
FEC.
Configuration in the
Remote Controller bus
node operating
mode
1. Make sure that DIL switch DIL1.1 of the bus node is in
the remote controller position
(DIL1.1 = ON, DIL1.2 = OFF; see Tab.1/1).
2. Carry out the station selection (see section 2.1.4).
3. Drag module CPX−FB13: Remote Controller Mode" onto
line 0 of the configuration table (see diagram below).
The field bus node is
thus configured as Remote
Controller.
Use of Festo Software Tools Version 4 (FST4) is required
(see step 4.) to configure the CPX−FEC and CPX terminal.
4. Configure the CPX terminal with the Festo Software Tools
FST4 via the CPX−FEC.