2. Commissioning
2−49
Festo P.BE−CPX−FB13−EN en 0811c
Possibilities for parameterising the diagnostic memory
mode
Stop after 40 records...":
The first 40 diagnostic messages are saved, but after that
no further messages are saved.
Record continually...":
Continuous saving of the diagnostic messages. After the
40th message,
the oldest message will be overwritten.
There are two ways in which the diagnostic messages can be
saved:
... remanent":
The diagnostic messages remain saved when the oper
ating voltage is switched off or after a power failure.
without remanent":
The diagnostic messages will be lost when the operating
voltage is switched off
or after a power failure.
Possibilities for parameterising the fault end filter of the
diagnostic memory
You can parameterise whether a rectified fault (Outgoing
fault") is to be recorded in the diagnostic memory.
Record Coming/going":
When a fault occurs and is eliminated, the fault number
and the time of the event are recorded.
Record coming only":
Only when a fault occurs, the fault number and the time of
the event are recorded. If the fault is eliminated, the time
of the event will not be recorded.