120 MS-9050 Series Manual — P/N 52413:F 10/22/2010
Programming Master Programming Level
ANN-SECONDARY Options Screen
Pressing 3 while viewing ANN-BUS screen #2 will display the following screen:
The ANN-SECONDARY must be enabled if any modules are connected to the ANN-SEC option
card at J13. To enable the Secondary ANN-BUS, press 1 while viewing ANN-SECONDARY
screen so that the display reads ANN-SECONDARY Enabled Yes. Each press of the 1 key will
cause the display to toggle between ANN-SECONDARY Enabled Yes and ANN-SECONDARY
Enabled No. The factory default setting is ANN-SECONDARY Enabled No.
Onboard DACT
The Onboard DACT (Digital Alarm Communicator/Transmitter) provides communication to a cen-
tral station. Pressing 2 while viewing the Option Module Screen will cause the following screens
to be displayed:
Onboard DACT Enable
To enable the onboard DACT, press 1 while viewing Onboard DACT Screen #1 until the display
reads Enabled Yes. The display will toggle between Enabled Yes and Enabled No with each press
of the key. The factory default setting is Enabled No.
ANN-SECONDARY
1=ENABLED NO
OPTION MODULES
1=ANN-BUS
2=ONBOARD DACT
3=FUTURE USE
Option Module Screen
ON BOARD DACT
1=ENABLED YES
2=PRIMARY PHONE
3=SECONDARY PHONE
On Board DACT Screen #1
ON BOARD DACT
1=RING COUNT 03
2=CENTRAL STATION
3=MANUAL DIAL MODE
On Board DACT Screen #2
ON BOARD DACT
1=SUPERV PHONE LINE
On Board DACT Screen #3