MS-9050 Series Manual — P/N 52413:F 10/22/2010 189
Appendix B: Default Programming
The following table provides a list of the programming options and their factory default settings.
Program Option Factory Default Program Option Factory Default
Master Password 00000 NAC 1 & 2 Enable Enabled
Maintenance Password 11111 NAC 1 & 2 Silenceable Yes
Detector Programming Not Installed NAC 1 & 2 Type Bell
Detector Type Smoke-Photo NAC 1 & 2 Sync Type System Sensor
Detector Verification Off NAC 1 & 2 Autosilence 0
Detector Walktest Yes NAC 1 & 2 Coding Steady
Detector PAS No NAC 1 & 2 Zones Zone 000 only
Detector Presignal No NAC 1 & 2 Silence Inhibit No
Detector Zone Assign. 000 only Relay 1 Alarm
Detector Adj/Noun none Relay 2 Trouble (fixed)
Module Programming Not Installed Relay 3 Supervisory
Module Type Monitor Trouble Call Limit 0
Module Walktest Yes ANN-BUS Enabled No
(not used) Onboard DACT Enabled No
Module Presignal No Ring Count 0
Module Zone Assign. 000 only Central Station Reporting Disabled
Module Adj/Noun none DACT Backup Reporting First Available
Zone 0 Enable Enabled DACT Report Style By Point
Zone 1 Enable Enabled Central Station 1 & 2 Account Code 0000
Zone 2 Enable Enabled Central Station 1 & 2 Test Time 0000
Zone 3 Enable Enabled Central Station 1 & 2 Test Time Interval 24 Hour
.........................through.......... ..................... Central Station 1 & 2 Phone Number
Zone 19 Enable Enabled Central Station 1 & 2 Format Ademco Contact ID
Zone 0 Type Monitor Line 1 Touchtone/Rotary Touchtone
.......................through........ Line 2 Touchtone/Rotary Touchtone
Zone 19 Type Monitor Supervise Phone Line 2 Yes
Special Purpose Zones 17, 18, 19 No ANN-BUS Enabled No
Loop Style Style 4 ANN-S/PG Port Parallel
Loop Protocol CLIP (fixed) ANN-S/PG Baud 9600
Trouble Reminder Off ANN-S/PG Data Bits 7
Banner ANN-S/PG Parity Even
Time Format 12 Hr ANN-S/PG Stop Bits 1
Hours Setting 12 ANN-S/PG Offline Timer 60
Minutes Setting 00 ANN-S/PG Printer Supervision No
AM-PM Setting AM ANN-80 Piezo Enabled Yes
Month Setting 01 ANN-80 Lock Enabled Yes
Day Setting 01 ANN-80 Acknowledge Button Enabled Yes
Year Setting 06 ANN-80 Silence Button Enabled Yes
Canadian Option Off ANN-80 Reset Button Enabled Yes
AC Loss Delay 2 Hours ANN-80 Drill Button Enabled Yes
Daylight Savings Enabled ANN-I/O Point/Zone Zone