36 MS-9050 Series Manual — P/N 52413:F 10/22/2010
Installation ANN-BUS Devices
3. Secure the ANN-SEC to the circuit board with the supplied screw.
2.9 ANN-BUS Devices
Guidelines
A variety of optional annuciation devices can be connected to an ANN-BUS communication
circuit. ANN Series devices can be connected to the primary communication circuit (EIA-485)
terminals on TB3. A secondary communication circuit (EIA-485) for these devices is available
at TB1 on the ANN-SEC card.
When using one ANN-BUS circuit, up to eight (8) annunciators can be supported.
When using both ANN-BUS communication circuits, the primary circuit supports up to three
(3) annunciators and the secondary circuit supports up to (5) annunciators.
Compatible devices include:
ANN-80 LCD Annunciator
ANN-80C LCD Indicator (Canadian Applications)
ANN-S/PG Serial/Parallel Printer Interface Module
ANN-I/O LED Driver Module
ANN-LED Annunciator Module
ANN-RLED Annunciator Module (red alarm LEDs only)
ANN-RLY Relay Module
When operating two ANN-BUS circuits, only one ANN-S/PG Printer module can be used in
the system.
The panel is capable of operating a primary ANN-BUS (TB3) and a secondary ANN-BUS
(TB1 on ANN-SEC card) simultaneously.
2.9.1 ANN-BUS Wiring
This section contains information on calculating ANN-BUS wire distances and the types of wiring
configurations (Class B).
J13
T
B
1
J
1
ANN-SEC
FACP Circuit Board
connector to J13 on
main circuit board
standoff and screw
Figure 2.12 Installing the ANN-SEC Option Card
9050annsec.wmf
!
r
WARNING: RISK OF ELECTRICAL SHOCK
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING
ANY MODULES OR WIRING.