52 MS-9050 Series Manual — P/N 52413:F 10/22/2010
Section 3: Programming
3.1 Programming Data Entry
Programming can be accomplished using the MS-9050UD keypad or by connecting an optional
standard computer keyboard. The keyboard can be connected to the PS-2 connector J6 on the con-
trol panel main circuit board.
The information presented in this section refers to programming the MS-9050UD via the onboard
keypad. If an optional computer keyboard is connected to the MS-9050UD main circuit board, the
following table describes the keyboard keys which correspond to the onboard keypad keys.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for
Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific
values or not used at all as indicated below:
Program feature
or option
Permitted in
UL 864? (Y/N)
Possible settings
Settings permitted in UL
864
Trouble Call Limit N
Refer to “Trouble Call Limit (Dialer Runaway Prevention)” on
page 123.
Trouble Call Limit = 0 (factory default): unlimited calling to
Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique trouble
to from 1 to 99 within a 24 hour period
Trouble Call Limit = 0
for unlimited Central Station
trouble calls
Remote Download Y
Refer to “Remote Download” on page 177.
Remote Download - Proprietary No
Remote Download - Proprietary Yes
Remote Download
Proprietary Yes for
Proprietary Installations Only
Keypad Keys Computer Keyboard Keys
1st Event Home
CLR Delete
ESC Esc
RECALL Insert
**
##
A - Z A - Z
0 - 9 0 - 9
(on QZ key) Space bar
——
//
••




ENTER Enter
ACK/STEP F1
SILENCE F2
DRILL F3
RESET F4