MS-9050 Series Manual — P/N 52413:F 10/22/2010 89
Master Programming Level Programming
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Waterflow
silenceable
zone type to the selected zone. Any signaling devices programmed to the same zone can
be silenced by pressing the Alarm Silence key or by using the auto-silence feature.
To program a waterflow circuit as nonsilenceable
, refer to “System Setup” on page 90 and “Water-
flow Silenceable” on page 104.
Zones Available
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:
The display will show all of the zones that are still available for programming.
3.6.4 Loop Setup
Loop Setup allows the programmer to configure the SLC Loop for NFPA Style 4, 6 or 7 wiring and
to select the loop protocol. Pressing 1 while viewing Programming Screen #2 will cause the fol-
lowing screen to be displayed:
Style
To program the SLC Style for the loop, press 1 for Style, while viewing Loop Setup Screen. In the
preceding example, the control panel is programmed for Style 4 SLC wiring as indicated by the 4 to
the right of Style in the display. To change the style, press 1 to toggle the display to read Style 6.
Each press of the 1 key will cause the display to toggle between Style 4 and Style 6. Note that, when
programming the Loop Style, the programmer can only select between Style 4 and Style 6. To pro-
gram a system for Style 7 wiring, the programmer must select the Loop Setup for Style 6. Style 7
wiring is the same as Style 6 with the added requirement that each device on the loop must have a
pair of isolator modules, one on each side. The factory default setting is Style 4.
Note on SLC Troubles: If the FACP reports an open fault on an SLC Loop programmed for Style
6, the trouble condition will latch at the FACP. When the SLC Loop has been repaired, the Reset
button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired) to clear
the SLC trouble.
NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will
only change how it is reported to the Central Station.
NOTE: If a tornado zone is required, choose Zone Type “Hazard”.
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=FUTURE
Zone Setup Screen #3
ZONES AVAILABLE
01 02 03 04 05 06 07
08 09 10 11 12 13 14
15 16 17 18 19
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOP
Programming Screen #2
LOOP SETUP
1=STYLE 4
2=PROTOCOL CLIP
Loop Setup Screen