MS-9050 Series Manual — P/N 52413:F 10/22/2010 35
Optional Modules/Accessories Installation Installation
9. Test system for proper operation.
2.8.2 ANN-SEC Option Card
The ANN-SEC option card allows for a secondary ANN-BUS. Install the ANN-SEC as follows.
1. Remove the chassis mounting screw to the right of TB7 and replace it with the supplied 0.5” x
4-40 male-female standoff.
2. Install the header into J13 on the main circuit board.
Figure 2.11 4XTMF Connectors to MS-9050UD Connectors
J8 & J9 Connectors
Jumper JP2
Standoff
Standoff
4XTMF
MS-9050UD
9050ud4xtm.wmf
Jumper JP28
NOTE: Jumper JP2 on the FACP main circuit board can be used to configure the FACP
supervisory relay for operation with the 4XTMF module. Relay 3 at TB3 must be programmed as
a supervisory relay.
Removing the jumper from JP2 will allow the 4XTMF to generate a trouble if the supervisory
contact opens
Leaving the jumper on JP2 will prevent generation of a trouble if the supervisory contact opens