EasyManua.ls Logo

Fire-Lite MS-9050UD - Supervisory Operation

Fire-Lite MS-9050UD
220 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
152 MS-9050 Series Manual — P/N 52413:F 10/22/2010
Operating Instructions Supervisory Operation
A typical alarm display would be as illustrated below:
Note that the device type, which in this example is PULL STATION, can be any other programma-
ble alarm type.
The information displayed in the above example provides the following information:
First line in display:
The type of event; in this example ALARM indicating an alarm condition
Device type identifier; in this example, PULL STATION indicates a manual pull box. Other
device type identifiers which can be displayed include SMOKE (ION) for Ionization
Detector, HEAT for Heat Detector, CONTROL for Control Module, and MONITOR for
Monitor Module, PULL STATION for a manual pull box, etc. Refer to“Edit Detector” on
page 59,“Edit Module Screen for Monitor Module” on page 69 and“Edit Module Screen for
Control Modules” on page 78 for information on additional device types.
Second line in display:
<ADJ>; refers to the user programmed adjective descriptor from library list resident in the
control panel or custom entry via PC.
<NOUN>; refers to the user programmed noun descriptor from library list resident in the
control panel or custom entry via PC.
Third line in display: Z000 indicates the zone programmed to this device which, in this
example, is general alarm Zone 000. Note that a single device can be programmed to five
different zones but only the first zone will be displayed.
Fourth line in display:
Time; the current time in this example is 10:00A which represents 10:00 AM
Date; the current month, day and year in this example is 01 for January, 21 for the 21st day
of the month and 10 for the year 2010
Device Address; 1M001 in this example 1 represents SLC Loop, M represents a module,
and 001 represents device address 001
4.6 Supervisory Operation
Supervisory operation is similar to alarm operation but with the following differences:
The piezo sounder pulses ½ second On and ½ second Off
The Supervisory LED flashes ½ second On and ½ second Off
The LCD displays the status label Active Supervisory along with the device name, type,
address, adjective/noun, associated zones, and time/date
Communicate the supervisory condition to the Central Station
The supervisory relay is activated
The alarm relay is not
activated
Silenced alarms are resounded
Timers are not started
Store event in history buffer
Terminate upload or download communications
ALARM PULL STATION
<ADJ> <NOUN>
Z000
10:00A 012110 1M001

Table of Contents

Other manuals for Fire-Lite MS-9050UD

Related product manuals