EasyManua.ls Logo

Fire-Lite MS-9050UD - Loop Protocol; 5: System Setup

Fire-Lite MS-9050UD
220 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
90 MS-9050 Series Manual — P/N 52413:F 10/22/2010
Programming Master Programming Level
Loop Protocol
Loop Protocol refers to the SLC loop mode of operation. The only mode available is CLIP (Classic
Loop Interface Protocol) which is used for the older legacy addressable devices such as the M300
Series modules and detectors as well as the newer devices. Pressing 2 while viewing the Loop
Setup Screen will have no effect on programming.
Device Addressing
It is important to note that the MS-9050UD addressable device capacity is 50 detectors and con-
trol/monitor modules. Addressable devices must not
be set to addresses higher than 50. Program-
ming will not allow addresses higher than 50.
Important: Detectors and Modules cannot have the same address. For example, if a detector is
installed at address 04, you cannot also have a module at address 04.
Note that It is permissible to mix old and new addressable devices on the same loop.
3.6.5 System Setup
System Setup allows the programmer to configure the following control panel features:
Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during
a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will
continue to sound at these rates until the alarm or trouble condition is cleared. Trouble
Resound is independent of Trouble Reminder. If a silenced trouble condition is not cleared by
midnight, the panel will reactivate the trouble sounder.
Banner: This option allows the user to change the top two lines of the LCD display from the
factory default readout to a user defined readout when the control panel is in Normal condition.
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr),
date and daylight savings time feature into the FACP memory
Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay.
NACs: This feature allows the programmer to configure the control panel Notification
Appliance Circuits for a variety of options, such as circuit type, silenceable/nonsilenceable,
autosilence, coding, silence inhibit, zone assignment and enable/disable.
Relays: This option allows programming of two onboard relays for activation by various
control panel events, such as alarm, trouble, supervisory, etc.
Canadian Option: This option allows the automatic programming of the FACP to Canadian
specifications (refer to “Canadian Option” on page 104).
Important! For Canadian Applications, this option must be set to ON prior to any other panel
programming.
Waterflow Silenceable: This option provides the ability to silence any output circuit activated
by a monitor module programmed as a waterflow type.

Table of Contents

Other manuals for Fire-Lite MS-9050UD

Related product manuals