EasyManua.ls Logo

Fire-Lite MS-9050UD - Page 20

Fire-Lite MS-9050UD
220 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20 MS-9050 Series Manual — P/N 52413:F 10/22/2010
Product Description Optional Modules and Accessories
Battery Boxes
BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery
Charger. The battery box, which is red and is provided with knockouts, was designed specifically
to compliment mounting below the FACP.
BB-55F
The BB-55F battery box may be used to house two 26 AH batteries, two 60 AH batteries or one
100 AH battery. When the CHG-120F is mounted in the BB-55F, two 26 AH or one 60 AH battery
may also be housed in the battery box.
PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program an MS-9050UD
directly from most IBM compatible personal computers (PC), running Windows
®
XP (or newer).
MS-9050UD program files can also be created and stored on the PC and then downloaded to the
control panel. The part number PK-CD Kit includes the Windows-based Programming Utility soft-
ware on CD-ROM with online help file. A serial cable (P/N: PRT/PK-CABLE), which must be
purchased separately, is required for local connection of the PC to the RS-232 (PC/Printer) termi-
nals at TB3 of the MS-9050UD main circuit board. Remote programming requires that the PC
have a 2400 baud (or faster) modem.
Important: Remote modification of FACP programming requires that the panel be enabled for
remote download (refer to “Remote Download” on page 177). Remote interrogation of panel pro-
gramming, history logs, detector status, etc., is possible without enabling the remote download
option.
Battery Chargers
CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the FACP. The FACP bat-
tery charger must be disabled, by removing jumper JP30, when using the CHG-75. The charger
and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the charger
can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control
panel. Refer to the CHG-75 Manual for additional information.
CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the FACP. The FACP
battery charger must be disabled, by removing jumper JP30, when using the CHG-120F. The bat-
teries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet
away from the control panel. Note that when using the BB-55F for housing the charger and batter-
ies greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for addi-
tional information.
IPDACT, IPDACT-2, IPDACT-2UD - IP Communicator
The IPDACT, IPDACT-2, and IPDACT-2UD are a compact, Internet Protocol Communicators
designed to allow FACP status communication to a Central Station via the internet. No telephone
lines are required when using any IPDACT. Using Contact ID protocol from the FACP, any
IPDACT converts the standard DACT phone communication to a protocol that can be transmitted
and received via the internet. It also checks connectivity between the FACP and Central Station.
Refer to the IPDACT Series Product Installation Document P/N 53109 for additional information.

Table of Contents

Other manuals for Fire-Lite MS-9050UD

Related product manuals