6 Mounting
6.2 Transducers FLUXUS F502TE
2020-05-29, UMFLUXUS_F502TEV1-5EN
36
• Select the installation instructions according to the supplied clasp:
Band clamp clasp
• Insert the tension strap into the tension strap clamp (2) (see Fig. 6.21).
• Place the tension strap around the pipe and insert it into the clasp (see Fig. 6.22).
• Tighten the tension strap.
• Tighten the clasp screw.
• Tighten the nut of the tension strap clamp (2), but not too firmly in order not to damage the tension strap (see Fig. 6.21).
Quick release clasp
• Insert the tension strap into the tension strap clamp (2) and the metal spring (see Fig. 6.23 and Fig. 6.21).
• Place the tension strap around the pipe and insert it into the clasp.
• Position the metal spring opposite to the tension strap clamp (2).
• Tighten the tension strap.
• Tighten the clasp screw.
• Tighten the nut of the tension strap clamp (2), but not too firmly in order not to damage the tension strap (see Fig. 6.21).
Fig. 6.20: Rail mounted on one side of the pipe
1 – tension strap clamp
2 – tension strap clamp
3 – nut
Fig. 6.21: Rail on the pipe
1 – tension strap clamp
2 – tension strap clamp
3 – metal spring
4 – nut
5 – clasp