EasyManua.ls Logo

Fluke endurance series - PROFINET IO Diagnostics

Fluke endurance series
147 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PROFINET IO
Input Data
69
9
9.4 Input Data
Table 9-3: Input Data
Address without offset
Length
Format
Value
0
4 Byte
REAL (Big Endian, Motorola)
Target Temperature 2 color
4
4 Byte
REAL (Big Endian, Motorola)
Target Temperature 1 color wide
8
4 Byte
REAL (Big Endian, Motorola)
Target Temperature 1 color narrow
12
4 Byte
REAL (Big Endian, Motorola)
Internal temperature
16
4 Byte
DWORD
Error Code
20
1 Byte
BYTE Bit0 (Bool)
Trigger state (0 reset, 1 set)
21
2 Byte
INT (Big Endian, Motorola)
Measured attenuation
9.5 Output Data
The output data may be used to change the initialization of the device (which was set once at start-up) when the
bus is in data exchange mode.
Table 9-4: Output Data
Address without offset
Length
Format
Value
0
1 Byte
BYTE
Type of parameter
1
4 Byte
REAL/ WORD
Parameter
The <Type of parameter> gives the meaning of the following parameters with the same format as described in
section 9.2 Parameters, page 67.
Table 9-5: Parameter Types
Type of parameter
Meaning
Format
0
Do not change anything
1
Slope
REAL
2
Emissivity
REAL
3
Transmissivity
REAL
4
Averaging time
REAL
5
Peak hold time
REAL
6
Valley hold time
REAL
7
Set point for the relay
REAL
8
Laser control
WORD
If <Type of parameter> is set to 0 then the output data gets ignored. As default, it should be set to 0 (zero).
9.6 Diagnostics
The diagnostics information of the fieldbus communicator can be read out acyclically using standard diagnostics
data sets defined in the PROFINET IO specification.
Errors occurring when configuring and setting the parameters of the fieldbus communicator and the connected
pyrometer as well as external errors are reported by the communicator via channel specific diagnostic.

Table of Contents

Related product manuals