7.5 Multiple Sensors
For an installation of two or more sensors in a RS485 network (2-wire, half duplex), each sensor needs its specific
RS485 network address (1 32) set via the control panel or alternatively via an ASCII command. Once all the units
are addressed, wire up the units in the 2-wire multidrop manner, whereas all A and B signals must be connected
to common lines. The common A signals must be routed to the TX+ and the common B signals to TX- terminal at
the USB/RS485 converter.
Addressing
If you are installing two or more sensors in a multi-drop configuration, please be aware of the following:
Each sensor must have a unique address greater zero (1 32).
Each sensor must be set to the same baud rate (default is 38.4 kBaud).
Once all the units are addressed, wire up the units in the 2-wire multidrop manner, keeping all A & B to
be common.
Now you can run the supplied software, as well as written communication software or an individual
terminal program to access the sensor for issuing commands and receive the responses.
Figure 7-4: Wiring Multiple Sensors via RS485 Interface with USB/RS485 Converter
A of 3
rd
sensor
B of 3
rd
sensor
A of 2
nd
sensor
B of 2
nd
sensor
To the 1
st
sensor