6.2.4 Interface Menu
INTERFACE
RS485 BAUD RATE
115200 bps
MULTIDROP ADDR.
000
RS485 MODE
TWO WIRE
TERMIN. RESISTOR
OFF
DHCP/BOOTP
OFF
ETHERNET IP
192.168.42.132
ETHERNET NM
255.255.255.0
ETHERNET GW
192.168.42.1
ETHERNET PORT
6363
WEB SERVER
ON
RS485 BAUD RATE
sets the baud rate for the RS485 communication:
1200, 2400, 9600, 19200, 38400 (default), 57600, 115200 bps
MULTIDROP ADDR.
sets the multidrop address to the sensor. A unique address is mandatory for each sensor in a RS485 network. The
valid address range is from 000 to 032
For more information, see section 7 RS485, page 60.
RS485 MODE
defines the RS485 communication mode with TWO WIRE (half-duplex). For Endurance compact sensors are no
other settings possible.
TERMIN. RESISTOR
activates/deactivates the sensor internal shunt resistor for the physically last unit in the RS485 network, see section
7.2 Installation, page 60.
DHCP/BOOTP
refers to a network mechanism to obtain a dynamic Ethernet address for the sensor: