101364     Model FT2 
3.8.  Resetting Total and Elapsed Time 
 
Pressing F3 and F4 at the same time in the normal running mode brings the prompt to reset the 
totalizer and elapsed time: 
 
 
Reset Total ? 
NO              YES 
F1  F2  F3  F4 
 
 
 
 
 
 
  If the password is active the program will prompt the user to enter the password: 
 
 
 
PASWD: 
UP       DN        NXT         OK 
F1  F2  F3  F4 
 
 
 
 
 
 
If the password is correct, the reset will be performed, otherwise a “Wrong Password” message will be 
displayed briefly before returning to the normal mode. 
 
  Note: To disable the programmable password set it to “0”. 
 
3.9.  Alarm Indications 
 
Alarm indications are provided to indicate any malfunctions, out of range values or saturated analog 
outputs. 
 
  The following list is a description of alarm codes: 
 
Code Description 
12  Power up Initializing 
13  Flow rate above high limit 
14  Flow below low limit 
15  Temperature above high limit 
16  Temperature below low limit 
22  Sensor out of range 
23  Velocity out of calibration table range 
24 Check settings 
25 Simulation mode 
26  Frequency output over range 
32  4 to 20 mA for flow rate is out of range 
33  4 to 20 mA for temperature is out of range 
34  ANYBUS communication error 
35 RTC Error 
36  EEPROM CRC Error 
37 Totalizer error detected 
 
Fox Thermal Instruments Inc., 399 Reservation Road, Marina, CA 93933  Page 27