PV series Solar Pumping Inverter
- 31 -
F11.12
Selection of failsafe
action 3
Ones: Disconnection Fault of
Temperature Sensor(Err24)
0:Reporting faults and freely
parking
1:Alarming and parking by
deceleration mode
2:Alarm and continue running
on fault frequency
3:Protection Invalid
00
×
Tens: Inverter load-lost(Err25)
F11.14
When failure, frequency
selection of continue
running
0:Running on current setting
frequency
0
×
1:Running on setting frequency
2:Running on upper-limit
frequency
3:Running on lower-limit
frequency
4:Running on abnormal
spare-frequency
F11.15
Abnormal Alternate
Frequency
0.00~Fmax
0.00Hz
×
F11.17
Protection time of Motor
Overload
30.0~300.0s
60.0s
×
F11.18
Selection of Overload
Pre-warning
Ones: selection of detection
0:always detection
1:detection only when constant
speed
00
×
Tens: condition selection of
detection
0:responds to rated current of
motor
1:responds to rated current of
inverter
F11.19
Detectable Level of
Overload Pre-alarm
20.0~200.0%
130.0%
×
F11.20
Detectable Time of
Overload Pre-alarm
0.1~60.0s
5.0s
×
F11.21
Pre-alarm Temperature
50.0~100.0℃
70.0℃
×