9.2 Temperature Controller/Servo/Inverter Connection 9-69
9.2.5 MR-J3-*T
Communication Setting
Editor
Communication setting
(Underlined setting: default)
Servo amplifier
Extension setting parameters
To make the parameter setting valid, the power supply is turned on again.
(Underlined setting: default)
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Item Setting Remarks
Connection Mode
1:1 / 1:n
/ Multi-link2 /
Multi-link2 (Ethernet) /
1:n Multi-link2 (Ethernet)
Signal Level RS-232C / RS-422/485
Baud Rate 9600 / 19200 / 38400 / 57600 / 115K bps
Data Length 8 bits (fixed)
Stop Bit 1 bit (fixed)
Parity Even (fixed)
Targe t Port No. 0
to 31
Parameter
No.
Symbol Item Setting Example
PC20 SNO Station number setting 0
to 31
PC21 SOP Communication function selection
00
Response delay time
0: Invalid
1: Valid
Baud rate
0: 9600 bps
1: 19200 bps
2: 38400 bps
3: 57600 bps
4: 115200 bps
Device Memory TYPE Remarks
F01 (status display) 00H Real number, read only
12 (external I/O signals) 03H Double-word, partially read only
33 (alarm history) 04H Double-word, read only
02 (current alarm) 05H Read only
F35 (status display at alarm occurrence) 06H Real number, read only
42 (other commands) 0DH Double-word, read only
81 (status display data erasure) 0EH Write only
82 (alarm history erasure) 0FH Write only
8B (operation mode selection) 10H
90 (I/O device prohibition/cancel) 11H Write only
92 (input device ON/OFF) 12H Double-word, write only
A0 (test operation mode data) 13H Double-word, write only
S01 (status display name and unit) 14H Read only
04 (parameters) 15H
05A (basic setting parameters) 16H Double-word
05B (gain/filter parameters) 17H Double-word
05C (extension setting parameters) 18H Double-word
05D (I/O setting parameters) 19H Double-word
F05A (basic setting parameters) 1AH Real number
F05B (gain/filter parameters) 1BH Real number
F05C (extension setting parameters) 1CH Real number
F05D (I/O setting parameters) 1DH Real number