13.2 Temperature Controller/Servo/Inverter Connection 13-35
13.2.4 E5AR/E5ER
Communication Setting
Editor
Communication setting
(Underlined setting: default)
Temperature Controller
Communication level setting (LS)
(Underlined setting: default)
*1 When writing setting data from the V9, set “ON” for the “communication writing” setting.
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Item Setting Remarks
Connection Mode
1:1 / 1:n
/ Multi-link2 / Multi-link2 (Ethernet) /
1:n Multi-link2 (Ethernet)
Signal Level RS-422/485
Baud Rate 9600
/ 19200 / 38400 bps
Data Length 7
/ 8 bits
Stop Bit 1 / 2
bits
Parity None / Odd / Even
Targe t Port No. 0 to 31
Level Displayed Character Setting Data Setting
Communication level
(L.S)
PSEL Protocol selection CompoWay/F
U-no Communication unit No. 0 to 31
bps Baud rate 9600
/ 19200 / 38400 bps
LEn Communication data length 7
/ 8 bits
Sbit Communication stop bit 1 / 2
bits
Prty Communication parity None / Odd / Even
Adjustment level
(L.Adj)
CMWT
Communication writing
*1
OFF / ON
Device Memory TYPE Remarks
C0 (communication monitor) 00H Double-word
C1 (communication monitor) 01H Double-word
C4 (communication monitor) 03H Double-word
C5 (protection level) 04H Double-word
C6 (run level) 05H Double-word
C7 (adjustment level) 06H Double-word
C8 (adjustment 2 level) 07H Double-word
C9 (bank setting level) 08H Double-word
CA (PID setting level) 09H Double-word
CB (approximation setting level) 0AH Double-word
CC (default setting level for input) 0BH Double-word
CD (default setting level for control) 0CH Double-word
CE (default setting level 2 for control) 0DH Double-word
CF (warning setting level) 0EH Double-word
D0 (display adjustment level) 0FH Double-word
D1 (communication level) 10H Double-word
D2 (high-performance setting level) 11H Double-word
D3 (extended control setting level) 12H Double-word