13-36 13. OMRON
Indirect Device Memory Designation
For bit designation, an expansion code setting is required.
00H: when designating bit 0 to 15
01H: when designating bit 16 to 31
PLC_CTL
Macro command “PLC_CTL F0 F1 F2”
15 8 7 0
n + 0 Model (91 to 98) Device type
n + 1 Address No.
n + 2 Expansion code Bit designation
n + 3 00 Station number
Contents F0 F1 (= $u n) F2
Read controller status
1 - 8
(PLC1 - 8)
n Station number
2
n + 1 Command: 0006H
n + 2
Status
n + 3
Relevant information
Operation instructions
1 - 8
(PLC1 - 8)
n
Station number
*1
3
n + 1 Command: 0030H
n + 2
Communication writing
0000H: Communication writing OFF (disabled)
0001H: Communication writing ON (enabled)
Control start/stop
0100H: Channel 1 RUN
0101H: Channel 1 STOP
0110H: Channel 2 RUN
0111H: Channel 2 STOP
0120H: Channel 3 RUN
0121H: Channel 3 STOP
0130H: Channel 4 RUN
0131H: Channel 4 STOP
01F0H: All channels Run
01F1H: All channels Stop
Bank selection
0200 to 0207H: Channel 1 Bank Nos. 0 to 7
0210 to 0217H: Channel 2 Bank Nos. 0 to 7
0220 to 0227H: Channel 3 Bank Nos. 0 to 7
0230 to 0237H: Channel 4 Bank Nos. 0 to 7
02F0 to 02F7H: All channels Bank Nos. 0 to 7
AT execution
0300H: Channel 1 PID group number currently selected
0301 to 0308H: Channel 1 PID group Nos. 1 to 8 designation
0310H: Channel 2 PID group number currently selected
0311 to 0318H: Channel 2 PID group Nos. 1 to 8 designation
0320H: Channel 3 PID group number currently selected
0321 to 0328H: Channel 3 PID group Nos. 1 to 8 designation
0330H: Channel 4 PID group number currently selected
0331 to 0338H: Channel 4 PID group Nos. 1 to 8 designation
03F0H: All channels PID group number currently selected
03F1 to 03F8H: All channels PID group Nos. 1 to 8 designation
Bit - 76543210
ch4 ch3 ch2 ch1
Bit Operation status
00 Control in progress
01 Error occurring (outputting manipulated variables at an
occurrence of error)
10 Resetting (including setting area 1)
11 Manual mode
Bit - 76543210
RSP input error
Potentiometer error
Beyond the display range
Input error
Blank Blank

Table of Contents