13.2 Temperature Controller/Servo/Inverter Connection 13-47
PLC_CTL
Macro command “PLC_CTL F0 F1 F2”
Return data: Data stored from temperature controller to V series
Contents F0 F1 (= $u n) F2
Auto tuning
1 - 8
(PLC1 - 8)
n Station number
3
n + 1 Command: 0
n + 2
0 - 7: AT start channel No.
10: Collective start at all channels
11: Sequential start at all channels
12: Cancel
Lamp value setting
1 - 8
(PLC1 - 8)
n Station number
5
n + 1 Command: 1
n + 2 Bank No. / channel No.
n + 3 Lamp value
n + 4
Unit of time
0: Second
1: Minute
2: Hour
Lamp value read out
1 - 8
(PLC1 - 8)
n Station number
3
n + 1 Command: 2
n + 2 Bank No. / channel No.
n + 3 Lamp value
n + 4
Unit of time
0: Second
1: Minute
2: Hour
Setting data
1 - 8
(PLC1 - 8)
n Station number
3
n + 1 Command: 3
n + 2
0: Save
1: Initialize
Operation control
1 - 8
(PLC1 - 8)
n Station number
4
n + 1 Command: 4
n + 2
0: Control start
1: Control stop
n + 3 Channel No.
Manual operation
1 - 8
(PLC1 - 8)
n Station number
3
n + 1 Command: 5
n + 2 Channel No.