CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG99
2B55 Digital Input 3 Alarm Events 0 1 1 - F103 0
2B56 Digital Input 3 Trip 0 2 1 - F115 0
2B57 Digital Input 3 Trip Relays 0 6 1 - F111 0
2B58 Digital Input 3 Trip Delay 1 50000 1 100ms F2 50
2B59 Digital Input 3 Assignable Function 0 3 1 - F163 0
... Reserved
RRTD 1 – TEST OUPUT RELAYS
2B60 Force Trip Relay 0 2 1 - F150 0
2B61 Force Trip Relay Duration 0 300 1 s F1 0
2B62 Force AUX1 Relay 0 2 1 - F150 0
2B63 Force AUX1 Relay Duration 0 300 1 s F1 0
2B64 Force AUX2 Relay 0 2 1 - F150 0
2B65 Force AUX2 Relay Duration 0 300 1 s F1 0
2B66 Force Alarm Relay 0 2 1 - F150 0
2B67 Force Alarm Relay Range 01 300 1 s F1 0
... Reserved
RRTD 2 – TEST OUPUT RELAYS
2B70 Force Trip Relay 0 2 1 - F150 0
2B71 Force Trip Relay Duration 0 300 1 s F1 0
2B72 Force AUX1 Relay 0 2 1 - F150 0
2B73 Force AUX1 Relay Duration 0 300 1 s F1 0
2B74 Force AUX2 Relay 0 2 1 - F150 0
2B75 Force AUX2 Relay Duration 0 300 1 s F1 0
2B76 Force Alarm Relay 0 2 1 - F150 0
2B77 Force Alarm Relay Range 0 300 1 s F1 0
... Reserved
RRTD 3 – TEST OUPUT RELAYS
2B80 Force Trip Relay 0 2 1 - F150 0
2B81 Force Trip Relay Duration 0 300 1 s F1 0
2B82 Force AUX1 Relay 0 2 1 - F150 0
2B83 Force AUX1 Relay Duration 0 300 1 s F1 0
2B84 Force AUX2 Relay 0 2 1 - F150 0
2B85 Force AUX2 Relay Duration 0 300 1 s F1 0
2B86 Force Alarm Relay 0 2 1 - F150 0
2B87 Force Alarm Relay Range 0 300 1 s F1 0
... Reserved
RRTD 4 – TEST OUPUT RELAYS
2B90 Force Trip Relay 0 2 1 - F150 0
2B91 Force Trip Relay Duration 0 300 1 s F1 0
2B92 Force AUX1 Relay 0 2 1 - F150 0
2B93 Force AUX1 Relay Duration 0 300 1 s F1 0
2B94 Force AUX2 Relay 0 2 1 - F150 0
2B95 Force AUX2 Relay Duration 0 300 1 s F1 0
2B96 Force Alarm Relay 0 2 1 - F150 0
2B97 Force Alarm Relay Range 0 300 1 s F1 0
... Reserved
RRTD 1 – TEST ANALOG OUTPUTS
2BA0 Force Analog Outputs 0 1 1 - F126 0
2BA1 Analog Output 1 Forced Value 0 100 1 % range F1 0
2BA2 Analog Output 2 Forced Value 0 100 1 % range F1 0
2BA3 Analog Output 3 Forced Value 0 100 1 % range F1 0
2BA4 Analog Output 4 Forced Value 0 100 1 % range F1 0
... Reserved
RRTD 2 – TEST ANALOG OUTPUTS
2BB0 Force Analog Outputs 0 1 1 - F126 0
2BB1 Analog Output 1 Forced Value 0 100 1 % range F1 0
2BB2 Analog Output 2 Forced Value 0 100 1 % range F1 0
2BB3 Analog Output 3 Forced Value 0 100 1 % range F1 0
2BB4 Analog Output 4 Forced Value 0 100 1 % range F1 0
Table CG–10: MEMORY MAP (Sheet 54 of 57)
ADDR
(hex)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
FACTORY