CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG85
↓↓
24F3 8th Character of RRTD 3 - RTD #8 Name 32 127 1 - F1 " "
... Reserved
RRTD 3 – RTD #9
2500 RRTD 3 - RTD #9 Application 0 4 1 - F121 0
2501 RRTD 3 - RTD #9 High Alarm 0 2 1 - F115 0
2502 RRTD 3 - RTD #9 High Alarm Relays 0 7 1 - F113 2
2503 RRTD 3 - RTD #9 High Alarm Level 1 200 1 °C F1 130
2504 RRTD 3 - RTD #9 Alarm 0 2 1 - F115 0
2505 RRTD 3 - RTD #9 Alarm Relays 0 7 1 - F113 1
2506 RRTD 3 - RTD #9 Alarm Level 1 200 1 °C F1 130
2507 Record RRTD 3 - RTD #9 Alarms as Events 0 1 1 - F103 0
2508 RRTD 3 - RTD #9 Trip 0 2 1 - F115 0
2509 Enable RRTD 3 - RTD #9 Trip Voting 0 13 1 - F122 1
250A RRTD 3 - RTD #9 Trip Relays 0 7 1 - F111 1
250B RRTD 3 - RTD #9 Trip Level 1 200 1 °C F1 130
250C RRTD 3 - RTD #9 RTD Type 0 3 1 - F120 0
2510 First Character of RRTD 3 - RTD #9 Name 32 127 1 - F1 ’R’
↓↓
2513 8th Character of RRTD 3 - RTD #9 Name 32 127 1 - F1 " "
... Reserved
RRTD 3 – RTD #10
2520 RRTD 3 - RTD #10 Application 0 4 1 - F121 0
2521 RRTD 3 - RTD #10 High Alarm 0 2 1 - F115 0
2522 RRTD 3 - RTD #10 High Alarm Relays 0 7 1 - F113 2
2523 RRTD 3 - RTD #10 High Alarm Level 1 200 1 °C F1 130
2524 RRTD 3 - RTD #10 Alarm 0 2 1 - F115 0
2525 RRTD 3 - RTD #10 Alarm Relays 0 7 1 - F113 1
2526 RRTD 3 - RTD #10 Alarm Level 1 200 1 °C F1 130
2527
Record RRTD 3 - RTD #10 Alarms as
Events
0 1 1 - F103 0
2528 RRTD 3 - RTD #10 Trip 0 2 1 - F115 0
2529 Enable RRTD 3 - RTD#10 Trip Voting 0 13 1 - F122 1
252A RRTD 3 - RTD #10 Trip Relays 0 7 1 - F111 1
252B RRTD 3 - RTD #10 Trip Level 1 200 1 °C F1 130
252C RRTD 3 - RTD #10 RTD Type 0 3 1 - F120 0
2530 First Character of RRTD 3 - RTD #10 Name 32 127 1 - F1 ’R’
↓↓
2533 8th Character of RRTD 3 - RTD #10 Name 32 127 1 - F1 " "
... Reserved
RRTD 3 – RTD #11
2540 RRTD 3 - RTD #11 Application 0 4 1 - F121 0
2541 RRTD 3 - RTD #11 High Alarm 0 2 1 - F115 0
2542 RRTD 3 - RTD #11 High Alarm Relays 0 7 1 - F113 2
2543 RRTD 3 - RTD #11 High Alarm Level 1 200 1 °C F1 130
2544 RRTD 3 - RTD #11 Alarm 0 2 1 - F115 0
2545 RRTD 3 - RTD #11 Alarm Relays 0 7 1 - F113 1
2546 RRTD 3 - RTD #11 Alarm Level 1 200 1 °C F1 130
2547
Record RRTD 3 - RTD #11 Alarms as
Events
0 1 1 - F103 0
2548 RRTD 3 - RTD #11 Trip 0 2 1 - F115 0
2549 Enable RRTD 3 - RTD #11 Trip Voting 0 13 1 - F122 1
254A RRTD 3 - RTD #11 Trip Relays 0 7 1 - F111 1
254B RRTD 3 - RTD #11 Trip Level 1 200 1 °C F1 130
254C RRTD 3 - RTD #11 RTD Type 0 3 1 - F120 0
2550 First Character of RRTD 3 - RTD #11 Name 32 127 1 - F1 ’R’
↓↓
2553 8th Character of RRTD 3 - RTD #11 Name 32 127 1 - F1 " "
... Reserved
Table CG–10: MEMORY MAP (Sheet 40 of 57)
ADDR
(hex)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
FACTORY
DEFAULT