CG72 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
1C24 Reverse Power Alarm Delay 5 300 1 s F2 1
1C25 Reverse Power Alarm Events 0 1 1 - F103 0
1C26 Reverse Power Trip 0 2 1 - F115 0
1C27 Assign Trip Relays 0 7 1 - F111 1
1C28 Reverse Power Trip Level 1 25000 1 kW F1 1
1C29 Reverse Power Trip Delay 5 300 1 s F2 1
... Reserved
ENHANCED MOTOR LEARNED DATA
1C70 Number of Starts to Average 1 5 1 - F1 5
1C71 Access Learned Data Record Number 0 65535 1 - F1 0
TRIP COUNTER
1C80 Trip Counter Alarm 0 2 1 - F115 0
1C81 Assign Alarm Relays 0 7 1 - F113 1
1C82 Alarm Pickup Level 0 50000 1 - F1 25
1C83 Trip Counter Alarm Events 0 1 1 - F103 0
... Reserved
STARTER FAILURE
1C90 Starter Failure Alarm 0 2 1 - F115 0
1C91 Starter Type 0 1 1 - F125 0
1C92 Assign Alarm Relays 0 7 1 - F113 1
1C93 Starter Failure Delay 10 1000 10 ms F1 100
1C94 Starter Failure Alarm Events 0 1 1 - F103 0
... Reserved
CURRENT DEMAND
1CD0 Current Demand Period 5 90 1 min F1 15
1CD1 Current Demand Alarm 0 2 1 - F115 0
1CD2 Assign Alarm Relays 0 7 1 - F113 1
1CD3 Current Demand Alarm Limit 0 65000 1 A F1 100
1CD5 Current Demand Alarm Events 0 1 1 - F103 0
... Reserved
KW DEMAND
1CE0 kW Demand Period 5 90 1 min F1 15
1CE1 kW Demand Alarm 0 2 1 - F115 0
1CE2 Assign Alarm Relays 0 7 1 - F113 1
1CE3 kW Demand Alarm Limit 1 50000 1 kW F1 100
1CE4 kW Demand Alarm Events 0 1 1 - F103 0
... Reserved
KVAR DEMAND
1CF0 kvar Demand Period 5 90 1 min F1 15
1CF1 kvar Demand Alarm 0 2 1 - F115 0
1CF2 Assign Alarm Relays 0 7 1 - F113 1
1CF3 kvar Demand Alarm Limit 1 50000 1 kvar F1 100
1CF4 kvar Demand Alarm Events 0 1 1 - F103 0
... Reserved
KVA DEMAND
1D00 kVA Demand Period 5 90 1 min F1 15
1D01 kVA Demand Alarm 0 2 1 - F115 0
1D02 Assign Alarm Relays 0 7 1 - F113 1
1D03 kVA Demand Alarm Limit 1 50000 1 kVA F1 100
1D04 kVA Demand Alarm Events 0 1 1 - F103 0
... Reserved
SELF-TEST RELAY
1D06 Assign Service Relay 0 7 1 - F113 0
... Reserved
ANALOG OUTPUTS
1D40 Enable Analog Output 1 0 1 1 - F103 0
1D41 Assign Analog Output 1 Output Range 0 2 1 - F26 0
1D42 Assign Analog Output 1 Parameter 0 35 1 - F127 0
1D43 Analog Output 1 Minimum TBD TBD 1 - F1 0
Table CG–10: MEMORY MAP (Sheet 27 of 57)
ADDR
(hex)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
FACTORY
DEFAULT