CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG57
0739 RRTD 4 - RTD # 10 Max. Temperature -40 200 1 °C F4 40
073A RRTD 4 - RTD # 11 Max. Temperature -40 200 1 °C F4 40
073B RRTD 4 - RTD # 12 Max. Temperature -40 200 1 °C F4 40
... Reserved
RRTD 1 TRIP COUNTER
0800 RRTD 1 - Stator RTD Trips 0 50000 1 - F1 0
0801 RRTD 1 - Bearing RTD Trips 0 50000 1 - F1 0
0802 RRTD 1 - Other RTD Trips 0 50000 1 - F1 0
0803 RRTD 1 - Ambient RTD Trips 0 50000 1 - F1 0
0804 RRTD 1 - Digital Input Trips 0 50000 1 - F1 0
... Reserved
RRTD 2 TRIP COUNTER
0810 RRTD 2 - Stator RTD Trips 0 50000 1 - F1 0
0811 RRTD 2 - Bearing RTD Trips 0 50000 1 - F1 0
0812 RRTD 2 - Other RTD Trips 0 50000 1 - F1 0
0813 RRTD 2 - Ambient RTD Trips 0 50000 1 - F1 0
0814 RRTD 2 - Digital Input Trips 0 50000 1 - F1 0
... Reserved
RRTD 3 TRIP COUNTER
0820 RRTD 3 - Stator RTD Trips 0 50000 1 - F1 0
0821 RRTD 3 - Bearing RTD Trips 0 50000 1 - F1 0
0822 RRTD 3 - Other RTD Trips 0 50000 1 - F1 0
0823 RRTD 3 - Ambient RTD Trips 0 50000 1 - F1 0
0824 RRTD 3 - Digital Input Trips 0 50000 1 - F1 0
... Reserved
RRTD 4 TRIP COUNTER
0830 RRTD 4 - Stator RTD Trips 0 50000 1 - F1 0
0831 RRTD 4 - Bearing RTD Trips 0 50000 1 - F1 0
0832 RRTD 4 - Other RTD Trips 0 50000 1 - F1 0
0833 RRTD 4 - Ambient RTD Trips 0 50000 1 - F1 0
0834 RRTD 4 - Digital Input Trips 0 50000 1 - F1 0
... Reserved
RRTD 1 DIGITAL INPUT STATUS
0840 Digital Input 3 0 1 1 - F131 0
0841 Digital Input 4 0 1 1 - F131 0
0842 Digital Input 6 0 1 1 - F131 0
0843 Digital Input 5 0 1 1 - F131 0
0844 Digital Input 2 0 1 1 - F131 0
0845 Digital Input 1 0 1 1 - F131 0
... Reserved
RRTD 2 DIGITAL INPUT STATUS
0850 Digital Input 3 0 1 1 - F131 0
0851 Digital Input 4 0 1 1 - F131 0
0852 Digital Input 6 0 1 1 - F131 0
0853 Digital Input 5 0 1 1 - F131 0
0854 Digital Input 2 0 1 1 - F131 0
0855 Digital Input 1 0 1 1 - F131 0
... Reserved
RRTD 3 DIGITAL INPUT STATUS
0860 Digital Input 3 0 1 1 - F131 0
0861 Digital Input 4 0 1 1 - F131 0
0862 Digital Input 6 0 1 1 - F131 0
0863 Digital Input 5 0 1 1 - F131 0
0864 Digital Input 2 0 1 1 - F131 0
0865 Digital Input 1 0 1 1 - F131 0
... Reserved
RRTD 4 DIGITAL INPUT STATUS
0870 Digital Input 3 0 1 1 - F131 0
0871 Digital Input 4 0 1 1 - F131 0
Table CG–10: MEMORY MAP (Sheet 12 of 57)
ADDR
(hex)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
FACTORY
DEFAULT