CGCOMMUNICATIONS GUIDE PROFIBUS-DP COMMUNICATIONS
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG7
66 AvgPhaseVoltage 2 0 0000 65000 FDE8 1 V F1 0
68 Frequency 2 0 0000 12000 2EE0 1 Hz F3 0
70 BackSpinFrequency 2 1 0001 12000 2EE0 1 Hz F3 0
72 PowerFactor 2 –99 FF9D 100 0064 1 – F21 0
74 RealPower–kW 2
–
32000
8300 32000 7D00 1 kW F4 0
76 RealPower–hp 2 0 0000 65000 FDE8 1 hp F1 0
78 ReactivePower 2
–
32000
8300 32000 7D00 1 kvar F4 0
80 ApparentPower 2 0 0000 65000 FDE8 1 kVA F1 0
82 MWh 2 0 0000 65535 FFFF 1 MWh F1 0
84 PositiveMvarh 2 0 0000 65535 FFFF 1
Mvar
h
F1 0
86 NegativeMvarh 2 0 0000 65535 FFFF 1
Mvar
h
F1 0
88 HottestStatorRtd 2 0 0000 12 000C 1 F2 0
90 HottestStatorRtdTemp 2 –40 FFD8 200 00C8 1 °C F4 –42
92 LocalRtd1 2 –40 FFD8 200 00C8 1 °C F4 –42
94 LocalRtd2 2 –40 FFD8 200 00C8 1 °C F4 –42
96 LocalRtd3 2 –40 FFD8 200 00C8 1 °C F4 –42
98 LocalRtd4 2 –40 FFD8 200 00C8 1 °C F4 –42
100 LocalRtd5 2 –40 FFD8 200 00C8 1 °C F4 –42
102 LocalRtd6 2 –40 FFD8 200 00C8 1 °C F4 –42
104 LocalRtd7 2 –40 FFD8 200 00C8 1 °C F4 –42
106 LocalRtd8 2 –40 FFD8 200 00C8 1 °C F4 –42
108 LocalRtd9 2 –40 FFD8 200 00C8 1 °C F4 –42
110 LocalRtd10 2 –40 FFD8 200 00C8 1 °C F4 –42
112 LocalRtd11 2 –40 FFD8 200 00C8 1 °C F4 –42
114 LocalRtd12 2 –40 FFD8 200 00C8 1 °C F4 –42
116 CurrentDemand 2 0 0000 50000 C350 1 A F1 0
118 RealPowerDemand 2 0 0000 50000 C350 1 kW F1 0
120 ReactivePowerDemand 2
–
32000
8300 32000 7D00 1 kvar F4 0
122 ApparentPowerDemand 2 0 0000 50000 C350 1 kVA F1 0
124 PeakCurrent 2 0 0000 65535 FFFF 1 A F1 0
126 PeakRealPower 2 0 0000 50000 C350 1 kW F1 0
128 PeakReactivePower 2
–
32000
8300 32000 7D00 1 kvar F4 0
Table CG–1: Profibus Input Data (Sheet 2 of 4)
OFFSET CYCLIC DATA
(ACTUAL VALUES)
LENGTH
(BYTES)
MINIMUM MAXIMUM STEP
VALUE
UNITS FORMAT
CODE
DEFAULT
VALUE HEX VALUE HEX