P44x/EN ST/Hb
P442, P444 (ST) 4-
Menu text Default setting
Setting range
Step size
Min Max
GROUP 1 – AUTORECLOSE
C/S on 3P Rcl DT1 Enabled Enabled, Disabled
Check synchronism on 3-pole reclosure during Dead Time 1
Enables or disables the control by the check synchronism logic of the 3P high speed
autoreclosure (HSAR) cycle during dead time 1 (check synchro 3P HSAR).
AUTORECLOSE LOCKOUT
Block A/R (Bit = 1 means
autoreclose blocked)
1111 1111 1111
1111 1111 1111
1111 111
Bit 0: block at T2
Bit 1: block at T3
Bit 2: block at Tzp
Bit 3: block for LoL Trip
Bit 4: block for I>1 Trip
Bit 5: block for I>2 Trip
Bit 6: block for V<1 Trip
Bit 7: block for V<2 Trip
Bit 8: block for V>1 Trip
Bit 9: block for V>2 trip
Bit 10 (0A): block for IN>1 Trip
Bit 11 (0B): block for IN>2 Trip
Bit 12 (0C): block for Aided D.E.F Trip
Bit 13 (0D): block for Zero. Seq. Power Trip
Bit 14 (0E): block for IN>3 Trip
Bit 15 (0F): block for IN>4 Trip
Bit 16 (10): block for PAP Trip
Bit 17 (11): block for Thermal Trip
Bit 18 (12): block for I2>1 Trip
Bit 19 (13): block for I2>2 Trip
Bit 20 (14): block for I2>3 Trip
Bit 21 (15): block for I2>4 Trip
Bit 22 (16): block for VN>1 Trip
Bit 23 (17): block for VN>2 Trip
Bit 24 (18): block at Tzq
Bit 25 (19): block for V<3 Trip
Bit 26 (1A): block for V<4 Trip
Bit 27 (1B): block for V>3 Trip
Bit 28 (1C): block for V>4 trip
Bit 29 (1D): block for I<1 Trip
Bit 30 (1E): block for I<2 Trip
Block A/R 2 111111 Bit 0: block for F<1 Trip
Bit 1: block for F<2 Trip
Bit 2: block for F<3 Trip
Bit 3: block for F<4 Trip
Bit 4: block for F>1 Trip
Bit 5: block for F>2 Trip
Set to 1 the relevant bit to block the autoreclose when the relevant fault occurs. It will cause
a lockout if autoreclose is in progress.