EasyManua.ls Logo

GE P444

GE P444
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P
44x/EN PL/Hb6
Programmable Logic
(PL) 6
-52 MiCOM 40 Agile
P442, P444
Ordinal English Text Description Source
395 Tzq Timer in zone Q elapsed (at 1 = end of timer) PSL
1097 TZq Timer Block Timer block TZq input PSL
1084 User Trip A
Internal input for trip logic A
Set to 1: Trip A Internal input managed with the
general trip logic(with A/R / Evolving fault…)
Can be assigned by external condition
PSL (IN) Trip
Logic
1085 User Trip B
Internal input for trip logic B
Set to 1: Trip B Internal input managed with the
general trip logic(with A/R / Evolving fault…)
Can be assigned by external condition
PSL (IN)
Trip Logic
1086 User Trip C
Internal input for trip logic C
Set to 1: Trip C Internal input managed with the
general trip logic(with A/R / Evolving fault…)
Can be assigned by external condition
PSL (IN)
Trip Logic
239 V< Dead Bus
Dead Bus: high when the Dead Bus condition is met
(voltage below the V<Dead Bus threshold value
(setting) - always calculated as a single phase voltage
reference.
PSL (OUT)
Synchro
Check
237 V< Dead Line
Dead Line: high when the Dead Line condition is met
(voltage below the 'V< Dead Line' threshold value
(setting) The measured voltage is always calculated
as a single phase voltage
PSL (OUT)
Synchro
Check
285 V< Start Any A Any undervoltage start detected on phase A
PSL (OUT)
Undervoltage
286 V< Start Any B Any undervoltage start detected on phase B
PSL (OUT)
Undervoltage
287 V< Start Any C Any undervoltage start detected on phase C
PSL (OUT)
Undervoltage
197 V<1 Alarm 1st stage undervoltage alarm picks up when V<1 starts
PSL (OUT)
V<1
288 V<1 Start Undervoltage 1
st
stage start (any phase)
PSL (OUT)
Undervoltage
371 V<1 Start A Undervoltage stage 1 pick up on phase A PSL
372 V<1 Start B Undervoltage stage 1 pick up on phase B PSL
373 V<1 Start C Undervoltage stage 1 pick up on phase C PSL
1069 V<1 Timer Block
Block phase undervoltage stage 1 time delay
Set to 1: 'V<1 Time Delay' will be blocked and V<1 will
start but will not issue any trip command.
Reset to 0: Opto input power off if signal assigned to
an opto input OR DDB at 0 if signal assigned to a DDB
cell
PSL (IN) V<1
290 V<1 Trip Undervoltage 1
st
stage – 3-phase trip
PSL (OUT)
Undervoltage
198 V<2 Alarm
2nd stage undervoltage alarm picks up when V<21
starts
PSL (OUT)
V<2
289 V<2 Start Undervoltage 2
nd
stage start (any phase)
PSL (OUT)
Undervoltage
374 V<2 Start A Undervoltage stage 2 pick up on phase A PSL
375 V<2 Start B Undervoltage stage 2 pick up on phase B PSL
376 V<2 Start C Undervoltage stage 2 pick up on phase C PSL
1070 V<2 Timer Block
Block phase undervoltage stage 2 time delay
Set to 1: 'V<2 Time Delay' will be blocked and V<1 will
start but will not issue any trip command.
Reset to 0: Opto input power off if signal assigned to
an opto input OR DDB at 0 if signal assigned to a DDB
cell
PSL (IN) V<2
291 V<2 Trip Undervoltage stage 2
nd
stage – 3-phase trip
PSL (OUT)
Undervoltage
396 V<3 Start Undervoltage stage 3 start PSL

Table of Contents

Related product manuals